The IQAir Cleanroom Series are configured with the hospital-grade HyperHEPA Class H13 filter. It can help to lower the airborne particles ranging from large dust to ultra-fine particles such as allergens, bacteria and viruses. As such, its application will reduce the chance of occupants from inhaling excessive particles, being infected by allergens, bacteria and viruses, as well as lower the potential risk of cross infection of infectious diseases such as cold and flu among the occupants. Also, the pre-filter and HEPA-filter of Cleanroom Series consists of antimicrobial media that is capable of destroying the growth of disease-causing microorganisms.
Besides controlling particulate matters, IQAir Cleanroom 250 has an independent gas and odour filter for the control of a wide range of chemical contaminants and odours.
2. Individually tested and certified for guaranteed filtration efficiency of ≧99.97% for particles with size ≧0.3 micron, and supplied with a hand-signed Certificate of Performance
3. Anti-tampering features designed to prevent unauthorized access to the replacement filters
4. Power cable inlet fixture helps to prevent unauthorized unplugging of the system
Air delivery per fan speed (incl. filters) | 1: 55 2: 100 3: 170 4: 250 5: 320 6: 450 m3/h |
Weight (incl. filters) (approx.) | ca. 16 kg |
Power requirements | 220-240 V / 50-60 Hz |
Energy consumption | ca. 20-135 W |
Dimensions (H x W x D) | 71 x 38 x 41 cm |
Fan motor | centrifugal, backward curved, with thermal protector, non-stop use approved |
Colour of main housing / locking arms | light grey / green |
Housing material | non-offgasing, impact-resistant, UV-stabilized ABS |
- ICUs
- Operating rooms
- Research & microbiology labs
- Food processing & packaging
- Critical data storage facilities
- Computer & server rooms
- Purpose: control of coarse, fine & ultra-fine dust particles; protection of subsequent filters
- Efficiency: ≧ 55% at ≧ 0.3 μm (class F8, antimicrobial type)
F2 - Gas & odour filter (V5-Cell Filter MG)
- Purpose: control of a wide range of chemical contaminants and odours
F3 - HEPA-filter (CR HyperHEPA Filter H13 (L) A)
- Purpose: control of fine & ultra-fine particulate matter incl. bacteria, viruses & mould spores
- Efficiency: ≧ 99.97% at ≧ 0.3 μm (class H13, antimicrobial type)
- 4 languages selection
- 6 selectable fan speeds settings
- Intelligent filter life monitor and filter replacement LEDs
- Advanced timer to allow programming of operating hours and weekdays
- Supplied with remote control & power cord with plug
- Supplied with casters for easy mobility